|Table of Contents|

[1] Wang Shugang, Zhang Tengfei, Zhang Jian,. Air interaction around outdoor air-cooled condensers [J]. Journal of Southeast University (English Edition), 2010, 26 (2): 222-226. [doi:10.3969/j.issn.1003-7985.2010.02.017]
Copy

Air interaction around outdoor air-cooled condensers()
Share:

Journal of Southeast University (English Edition)[ISSN:1003-7985/CN:32-1325/N]

Volumn:
26
Issue:
2010 2
Page:
222-226
Research Field:
Energy and Power Engineering
Publishing date:
2010-06-30

Info

Title:
Air interaction around outdoor air-cooled condensers
Author(s):
Wang Shugang Zhang Tengfei Zhang Jian
School of Civil Engineering, Dalian University of Technology, Dalian 116024, China
Keywords:
air-cooled condensers flow interaction heat transfer optimization computational fluid dynamics(CFD) measurement
PACS:
TU831
DOI:
10.3969/j.issn.1003-7985.2010.02.017
Abstract:
In order to increase cooling or heating efficiency, a porous computational fluid dynamics(CFD)model is employed to predict the thermo-fluid status and optimize the placement of outdoor units.A full scale model is established to validate the accuracy of CFD simulation in terms of velocity and temperature distributions.The comparison between the measurement and the simulation shows a good agreement.By evaluating the condensers’ sucked air temperature with CFD for three units installed in a row, it is found that the minimum separation distance among neighboring units is 0.2 m;a vertical wall should be apart from the unit line by at least 0.8 m;and large different operating pressures among units do not impact the flow rate and the heat transfer of the other units meaningfully.

References:

[1] Chow T T, Lin Z.Prediction of on-coil temperature of condensers installed at tall building re-entrant [J].Applied Thermal Engineering, 1999, 19(2):117-132.
[2] Chow T T, Lin Z, Wang Q W.Effect of building re-entrant shape on performance of air-cooled condensing units [J].Energy and Buildings, 2000, 32(2):143-152.
[3] Bojic M, Lee M, Yik F.Flow and temperature outside a high-rise residential building due to heat rejection by its air-conditioners [J].Energy and Buildings, 2001, 33(7):737-751.
[4] Bojic M, Lee M, Yik F, et al.Influence of clearances on the energy performance of window-type air-conditioners at the same level outside residential buildings [J].Building and Environment, 2002, 37(7):713-726.
[5] Yakhot V, Orzag S, Thangam S, et al.Development of turbulence models for shear flows by a double expansion technique [J].Phys Fluids A, 1992, 4(7):1510-1520.
[6] Zhang Z, Zhang W, Zhai Z, et al.Evaluation of various turbulence models in predicting airflow and turbulence in enclosed environments by CFD.Part-2:comparison with experimental data from literature [J].HVAC& R Research, 2007, 13(6):871-886.
[7] Fluent Inc.Fluent user’s guide [M].Fluent Inc, 2003.
[8] Vafai K.Convective flow and heat transfer in variable porosity media [J].Journal of Fluid Mechanics, 1984, 147(1):233-259.

Memo

Memo:
Biography: Wang Shugang(1963—), male, doctor, professor, sgwangln@yahoo.com.cn.
Citation: Wang Shugang, Zhang Tengfei, Zhang Jian.Air interaction around outdoor air-cooled condensers[J].Journal of Southeast University(English Edition), 2010, 26(2):222-226.
Last Update: 2010-06-20