|Table of Contents|

[1] Wang JinQian HuaZhang Xiaosong,. Influence of environmental conditionson airborne infection risk in ward [J]. Journal of Southeast University (English Edition), 2010, 26 (2): 266-269. [doi:10.3969/j.issn.1003-7985.2010.02.027]
Copy

Influence of environmental conditionson airborne infection risk in ward()
Share:

Journal of Southeast University (English Edition)[ISSN:1003-7985/CN:32-1325/N]

Volumn:
26
Issue:
2010 2
Page:
266-269
Research Field:
Energy and Power Engineering
Publishing date:
2010-06-30

Info

Title:
Influence of environmental conditionson airborne infection risk in ward
Author(s):
Wang JinQian HuaZhang Xiaosong
School of Energy and Environment, Southeast University, Nanjing 210096, China
Keywords:
airborne transmitted diseases air change per hour(ACH) ventilation rate
PACS:
TU834.3
DOI:
10.3969/j.issn.1003-7985.2010.02.027
Abstract:
In order to study the influence of parameters on airborne transmitted diseases in a hospital ward, a pollutant decay equation and a Wells-Riley model are adopted to study the relationship between the airborne infection risk and the parameters such as the ventilation rate, the number of susceptible persons and the volume of the ward.The results show that the airborne infection risk can be reduced by increasing the ventilation rate.For two wards with the same air change per hour(ACH)but different volumes, the ventilation rate in a large room is higher than that in a small one.The number of the infected persons in the ward increases with the increase in the susceptible persons when the ACH is a constant.Therefore, the ventilation rate in the ward is not only estimated by the ACH but also related to the volume of the ward and the number of the susceptible persons.

References:

[1] WHO. Influenza A(H1N1)—update 16 [EB/OL].(2009-05-05)[2009-06-20].http://www.who.int/csr/don/2009_05_05a/en/index.html.
[2] Li Y, Leung G M, Qian H, et al.Role of ventilation in airborne transmission of infectious agents in the built environment—a multidisciplinary systematic review [J].Indoor Air, 2007, 17(1):2-18.
[3] Wells W F.Airborne contagion and air hygiene:an ecological study of droplet infection [M].Cambridge, MA, USA:Harvard University Press, 1955.
[4] Li Y, Ching W H, Qian H, et al.An evaluation of the ventilation performance of new SARS isolation wards in nine hospitals in Hong Kong [J].Indoor Built Environ, 2007, 16(5):400-410.
[5] Tung Y C, Hu S C, Tsai T L, et al.An experimental study on ventilation efficiency of isolation room [J].Building and Environment, 2009, 44(2):271-279.
[6] Cheong K W D, Phua S Y.Development of ventilation design strategy for effective removal of pollutant in the isolation room of a hospital [J].Building and Environment, 2006, 41(9):1161-1170.
[7] Centers for Disease Control and Prevention.Guidelines for preventing the transmission of mycobacterium tuberculosis in health care facilities [EB/OL].(1998-10-28)[2009-06-20].http://wonder.cdc.gov/wonder/prevguid/m0035909/m0035909.asp.
[8] American Society of Heating, Refrigerating and Air-conditioning Engineers.Standard 62.2—2003 ventilation and acceptable indoor air quality in low-rise residential buildings [EB/OL].(2003-04-30)[2009-06-20].https://eweb.ashrae.org/eweb//DynamicPage.aspx?webCode=ProductDescr&prc_prd_key=5ead8117-8180-49a8-bd9f-96c3b9f21fd9.
[9] Centers for Disease Control and Prevention.Guidelines for preventing the transmission of mycobacterium tuberculosis in health care facilities [EB/OL].(2005-12-30)[2009-06-20].http://www.cdc.gov/mmwr/preview/mmwrhtml/rr5417 a1.htm?s_cid=rr5417a1_e.
[10] American Institute of Architects Academy of Architecture for Health.Guidelines for design and construction of hospital and health care work [S].Atlanta, GA, USA:American Institute of Architects Press, 2001.
[11] American Society of Heating, Refrigerating and Air-Conditioning Engineers.Standard 62.1—2004 ventilation for acceptable indoor air quality [EB/OL].(2004-04-06)[2009-06-20].https://eweb.ashrae.org/eweb//DynamicPage.aspx?webCode=ProductDescr&prc_prd_key=e987c52d-1e54-43e2-b024-868fd22c35f9.
[12] Wells W F.On air-borne infection study:droplets and droplet nuclei [J].Am J Hyg, 1934, 20(3):619-627.
[13] Riley E C, Murphy G, Riley R L.Airborne spread of measles in a suburban elementary school [J].Am J Epidemiol, 1978, 107(5):421-432.
[14] Nicas M, Nazaroff W W, Hubbard A.Toward understanding the risk of secondary airborne infection:emission of respirable pathogens[J].J Occup Environ Hyg, 2005, 2(3):143-154.
[15] Chen S C, Chang C F, Liao C M.Predictive models of control strategies involved in containing indoor airborne infections [J].Indoor Air, 2006, 16(6):469-481.
[16] Qian H, Li Y, Peter V N, et al.Spatial distribution of infection risk of SARS transmission in a hospital ward [J].Building and Environment, 2009, 44(8):1651-1658.
[17] Kantor H S, Poblete R, Pusateri S L.Nosocomial transmission of tuberculosis from unsuspected disease [J].Am J Med, 1988, 84(5):833-838.

Memo

Memo:
Biographies: Wang Jin(1985—), female, graduate;Qian Hua(corresponding author), male, doctor, associate professor, keenwa@gmail.com.
Citation: Wang Jin, Qian Hua, Zhang Xiaosong.Influence of environmental conditions on airborne infection risk in ward[J].Journal of Southeast University(English Edition), 2010, 26(2):266-269.
Last Update: 2010-06-20