|Table of Contents|

[1] Guo Jian, Lin Heyun, Fang Shuhua,. Analysis of input harmonic current mitigating performancein dual output phase-shift distribution transformer [J]. Journal of Southeast University (English Edition), 2012, 28 (2): 151-155. [doi:10.3969/j.issn.1003-7985.2012.02.004]
Copy

Analysis of input harmonic current mitigating performancein dual output phase-shift distribution transformer()
双输出移相配电变压器输入谐波电流抑制特性分析
Share:

Journal of Southeast University (English Edition)[ISSN:1003-7985/CN:32-1325/N]

Volumn:
28
Issue:
2012 2
Page:
151-155
Research Field:
Electrical Engineering
Publishing date:
2012-06-30

Info

Title:
Analysis of input harmonic current mitigating performancein dual output phase-shift distribution transformer
双输出移相配电变压器输入谐波电流抑制特性分析
Author(s):
Guo Jian1 Lin Heyun2 Fang Shuhua2
1School of Automation Engineering, Nanjing University of Aeronautics and Astronautics, Nanjing 210016, China
2 School of Electrical Engineering, Southeast University, Nanjing 210096, China
郭健1 林鹤云2 房淑华2
1南京航空航天大学自动化学院, 南京210016; 2东南大学电气工程学院, 南京210096
Keywords:
shift-phase transformer harmonic mitigating electromagnetic filtering field-circuit coupled method
移相变压器 谐波抑制 电磁滤波 场路耦合
PACS:
TM41
DOI:
10.3969/j.issn.1003-7985.2012.02.004
Abstract:
A novel dual output phase-shift distribution transformer(DOPSDT)is proposed based on the electromagnetic filtering theory. First, its structural characteristics, winding connection mode and turn number ratio for special phase shifting are investigated. Secondly, the balance formulation of harmonic magneto-motive forces is derived and the electromagnetic filtering principle of the DOPSDT is introduced. The harmonic mitigating performance under different nonlinear load conditions are also analyzed using the field-circuit coupled method. The analysis results show that the DOPSDT can mitigate the primary current distortion even under severe nonlinear load conditions. By applying the zero sequence flux cancellation and phase-shift techniques at their secondary windings, the DOPSDT can significantly reduce the 3rd, 5th, 7th, 9th, 15th, 17th and 19th harmonics within its secondary windings.
提出了一种基于电磁滤波原理的双输出移相配电变压器.首先, 研究了其结构布置特征、绕组联接方式及实现特定移相角的匝数匹配关系. 其次, 推导了该变压器的谐波磁势平衡方程, 论述了变压器实现电磁滤波的机理. 通过建立该变压器的场路耦合模型, 对不同非线性负载情况下的谐波抑制特性进行了分析计算. 研究结果表明, 在严重的非线性负载情况下, 双输出移相变压器仍可以有效抑制一次侧绕组输入电流的谐波;结合零序磁通消除技术和相移技术, 该变压器可以将配电系统中主要存在的3, 5, 7, 17和19倍次谐波电流抑制在二次绕组中.

References:

[1] Feng Jing. Source, harm and requlating measure of homonic pollution in the common power net [J]. Relay, 2003, 31(Sup): 39-41.(in Chinese)
[2] Jou H L, Wu J C, Wu K D. Analysis of zig-zag transformer applying in the three-phase four-wire distribution power system [J]. IEEE Transactions on Power Delivery, 2005, 20(2): 1168-1173.
[3] Zhou Lixia, Yin Zhongdong, Xiao Xiangning. Harmonic suppression in the electric propulsive shipping system based on phase-shifting reactor [J]. Transactions of China Electrotechnical Society, 2007, 22(8): 90-94.(in Chinese)
[4] Shi Jianfeng, Luo Longfu, Deng Shujuan, et al. Application of new type of propulsion transformer in harmonic suppression for ship power system [J]. Power System Technology, 2008, 32(21): 91-96; 102.(in Chinese)
[5] Luo Longfu, Li Ji, Xu Jiazhu, et al. Study on harmonic treatment based on new type converter transformer [J]. High Voltage Apparatus, 2006, 42(2): 96-98.(in Chinese)
[6] Kumbhar G B, Kulkarni S V. Analysis of sympathetic inrush phenomena in transformers using coupled field-circuit approach [C]//Power Engineering Society General Meeting. Tampa, FL, USA, 2007:1-6.
[7] Kumbhar G B, Kulkarni S V. Analysis of short-circuit performance of split-winding transformer using coupled field-circuit approach [J]. IEEE Transactions on Power Delivery, 2007, 22(2): 936-943.
[8] Liang Zhenguang, Tang Renyuan. Fault simulation of power transformers using 3d finite element model coupled to electric circuit equations [J]. Proceedings of the CSEE, 2003, 23(3): 137-140.(in Chinese)
[9] Tang R Y, Wang S H, Li Y, et al. Transient simulation of power transformers using 3D finite element model coupled to electric circuit equations [J]. IEEE Transactions on Magnetics, 2000, 36(4): 1417-1420.
[10] Guo Jian, Lin Heyun, Xu Zihong, et al. Calculation and analysis of branch currents of single spiral winding transformer based on field circuit coupled method [J]. Transactions of China Electrotechnical Society, 2010, 25(4): 65-70.(in Chinese)

Memo

Memo:
Biography: Guo Jian(1980—), male, doctor, lecturer, nuaaeelab_gj@nuaa.edu.cn.
Foundation items: The Program for Special Talent in Six Fields of Jiangsu Province(2011-ZBZZ-016), the Postdoctoral Science Foundation of Jiangsu Province(No.0902038C).
Citation: Guo Jian, Lin Heyun, Fang Shuhua. Analysis of input harmonic current mitigating performance in dual output phase-shift distribution transformer[J].Journal of Southeast University(English Edition), 2012, 28(2):151-155.[doi:10.3969/j.issn.1003-7985.2012.02.004]
Last Update: 2012-06-20