|Table of Contents|

[1] Wei Xiaoqing, Li Nianping, Zhou Hui, Xiao Shubo, et al. Investigation and analysis on indoor air qualityof large commercial office building in summer [J]. Journal of Southeast University (English Edition), 2010, 26 (2): 243-245. [doi:10.3969/j.issn.1003-7985.2010.02.021]
Copy

Investigation and analysis on indoor air qualityof large commercial office building in summer()
Share:

Journal of Southeast University (English Edition)[ISSN:1003-7985/CN:32-1325/N]

Volumn:
26
Issue:
2010 2
Page:
243-245
Research Field:
Environmental Science and Engineering
Publishing date:
2010-06-30

Info

Title:
Investigation and analysis on indoor air qualityof large commercial office building in summer
Author(s):
Wei Xiaoqing Li Nianping Zhou Hui Xiao Shubo Hu Lijun
College of Civil Engineering, Hunan University, Changsha 410082, China
Keywords:
large commercial office building indoor air quality(IAQ) objective evaluation subjective evaluation
PACS:
X820.2
DOI:
10.3969/j.issn.1003-7985.2010.02.021
Abstract:
To study the indoor air qualities(IAQ)of large commercial office buildings in Hunan province of China and the corresponding improvement methods, the IAQ of a large commercial office building in Changsha in July, 2008, is investigated.A questionnaire survey and field tests are used to collect data.According to the data of twelve rooms in this building, objective evaluation and the subjective evaluation of the IAQ are obtained.Almost all of the environmental parameters in these rooms basically meet the standards of the objective evaluation.But the average concentration of carbon dioxide in most rooms cannot reach the value of the cleanliness standards, 1 255 mg/m3.The average acceptability of the IAQ in these rooms is 71%, which is lower than the value of the ASHRAE 55—1992 standards, 80%.The proper increase in the wind speed and the indoor fresh air supply can greatly improve the objective evaluation and the subjective evaluation of the IAQ.

References:

[1] Yao Shouguang, Ma Zheshu, Cheng Ning, et al.Evolution and evaluation of research on indoor air quality[J].Journal of East China Shipbuilding Institute, 2002, 16(3):21-27.(in Chinese)
[2] World Health Organization.Indoor air pollutions:exposure and health effects[R].Geneva:WHO, 1983.
[3] Larry G, Berglund P E.Common elements in the design and operation of thermal comfort and ventilation systems [J].ASHRAE Transactions, 1994, 100(1):776-781.
[4] Collett C W, Ross J A, Sterling E M.Quality assurance strategies for investigating IAQ problems [J].ASHRAE Journal, 1994, 2(6):42-51.
[5] Burroughs H E B.IAQ:an environmental factor in the indoor habitat [J].Heating/Piping/Air Conditioning, 1997, 69(2):57-60.
[6] Burroughs H E B.Filtration:an investment in IAQ [J].Heating/Piping/Air Conditioning, 1997, 69(8):55-65.
[7] General Administration of Quality Supervision, Inspection and Quarantine of the People’s Republic of China.GB/T18883—2002 The indoor air quality standard[S].Beijing:Standards Press of China, 2002.(in Chinese)
[8] Shen Jinming.Indoor air quality evaluation & measures [D].Shanghai:College of Architecture and Urban Planning of Tongji University, 1996.(in Chinese)

Memo

Memo:
Biographies: Wei Xiaoqing(1981—), male, graduate;Li Nianping(corresponding author), male, doctor, professor, linianping@126.com.
Foundation item: The National Natural Science Foundation of China(No.50878078).
Citation: Wei Xiaoqing, Li Nianping, Zhou Hui, et al.Investigation and analysis on indoor air quality of large commercial office building in summer[J].Journal of Southeast University(English Edition), 2010, 26(2):243-245.
Last Update: 2010-06-20