Transmission cable fault detectorbased on waveform reconstruction()
一种具有波形复现功能的电缆故障测试仪
Share:

Journal of Southeast University (English Edition)[ISSN:1003-7985/CN:32-1325/N]

Volumn:
29
Issue:
2013 1
Page:
48-51
Research Field:
Automation
Publishing date:
2013-03-20

Info

Title:
Transmission cable fault detectorbased on waveform reconstruction
一种具有波形复现功能的电缆故障测试仪
Author(s):
Wu Jianfeng1 Yu Zhongzhou1 Li Jianqing1 Wang Lei2 Li Xiaoming1
1 School of Instrument Science and Engineering, Southeast University, Nanjing 210096, China
2 School of Automation, Nanjing Institute of Technology, Nanjing 210013, China
吴剑锋1 于忠洲1 李建清1 王蕾2 李小敏1
1东南大学仪器科学与工程学院, 南京 210096; 2南京工程学院自动化学院, 南京 210013
Keywords:
cable fault test waveform reconstruction fault position location time-domain pulse reflection
电缆故障检测 波形重构 故障点定位 时域脉冲反射
PACS:
TP216
DOI:
10.3969/j.issn.1003-7985.2013.01.010
Abstract:
In order to improve the accuracy of cable fault position location at a low cost and make the testing results intuitive, a cable fault detector based on waveform reconstruction is designed. In this detector, the cable fault position is located based on the time-domain pulse reflection(TDR)principle. A pulse waveform is injected in the tested cable, and a high-speed comparator with changeable reference voltages is used to binarize the test pulse waveform to a binary sequence on a certain voltage. Through scanning the reference voltage in a full voltage range, multi-sequences are acquired to reconstruct the pulse waveform transmission in the cable, and then the pulse attenuation feature, electrical open circuit fault, electrical short circuit fault, and the fault position of the cable are diagnosed. Experimental results show that the designed cable fault detector can determine the fault type and its position of the cable being tested, and the testing results are intuitive.
为了以较低成本提高电缆故障点的定位精度, 并且使测试结果更加直观, 设计了一种具有波形复现功能的电缆故障测试仪, 该测试仪采用时域脉冲反射原理进行电缆故障点定位.测试时, 首先将电磁脉冲加载到待测电缆, 依据相应高速比较器的参考电压将测试脉冲波形二值化获得单次测试位流数据, 然后将参考电压由高到低逐次扫描所得位流数据依次排列, 重构并复现测试脉冲波形, 进而可以得到电缆脉冲衰减特性、短路故障、断路故障及故障位置的诊断.实验测试结果表明, 该测试仪能够有效测定电缆的故障类型和位置, 测试结果直观.

References:

[1] Xu Binggeng, Li Shengxiang, Chen Zongjun. Communication cable line fault testing techniques [M]. Beijing: Beijing University of Posts and Telecommunications Press, 2000.(in Chinese)
[2] Dodds D E, Shafique M, Celaya M. TDR and FDR identification of bad splices in telephone cables[C]//Canadian Conference on Electrical and Computer Engineering. Ottawa, Canada, 2006:838-841.
[3] Guinee R A. A novel pulse echo correlation tester for transmission line fault location and identification using pseudorandom binary sequences[C]//34th Annual Conference of the IEEE Industrial Electronics Society. Orlando, Florida, USA, 2008: 1833-1838.
[4] Agilient Technologies. Time domain reflectometry theory application note 1304-2[EB/OL].(2006-05-10)[2012-06-10].http://cp.literature.agilent.com/litweb/pdf/5966-4855E.pdf.
[5] Horan D M, Guinee R. A novel pulse echo correlation tool for transmission path testing and fault finding using pseudorandom binary sequences[C]//IEEE International Symposium on Defect and Fault Tolerance in VLSI Systems. Monterey, CA, USA, 2005: 229-237.
[6] Vanaja R, Udayakumar K. Fault location in power transformers during impulse tests[C]//Proceedings of IEEE Power Engineering Society 2000 Winter Meeting. Singapore, 2000: 2199-2204.
[7] Anderson W E, Ramboz J D, Ondrejka A R. The detection of incipient faults in transmission cables using time domain reflectometry techniques: technical challenges[J]. IEEE Transactions on Power Apparatus and Systems, 1982, PAS-101(7):1928-1934.
[8] Xu Yi, Wu Jianfeng, Li Jianqing. Development of new multifunctional instrument for measuring faulted cables used in network[J]. Instrument Technique and Sensor, 2009(4):117-120.(in Chinese)
[9] Liu Y, Tong L, Zhu W X, et al. Impedance measurements of nonuniform transmission lines in time domain using an improved recursive multiple Reflection computation method[J]. Progress in Electromagnetics Research, 2011, 117:149-164.
[10] Wu Jianfeng, Li Jianqing, Wang Yinan, et al. A wired sensor network nodes ranging method[J]. Instrument Technique and Sensor, 2012(2):71-73.(in Chinese)
[11] Parkey C, Hughes C, Locken N. Analyzing artifacts in the time domain waveform to locate wire faults[J]. IEEE Instrumentation & Measurement Magazine, 2012, 15(4):16-21.
[12] Abboud L, Cozza A, Pichon L. A matched-pulse approach for soft-fault detection in complex wire networks[J]. IEEE Transactions on Instrumentation and Measurement, 2012, 61(6): 1719-1732.

Memo

Memo:
Biography: Wu Jianfeng(1975—), male, doctor, lecturer, wjf@seu.edu.cn.
Foundation items: The National Natural Science Foundation of China(No.61240032), the Natural Science Foundation of Jiangsu Province(No.BK2012560), the College Scientific and Technological Achievements Transformation Promotion Project of Jiangsu Province(No.JH-05), the Science and Technology Support Program of Jiangsu Province(No.BE2012740).
Citation: Wu Jianfeng, Yu Zhongzhou, Li Jianqing, et al.Transmission cable fault detector based on waveform reconstruction[J].Journal of Southeast University(English Edition), 2013, 29(1):48-51.[doi:10.3969/j.issn.1003-7985.2013.01.010]
Last Update: 2013-03-20